Glossary entry (derived from question below)
Spanish term or phrase:
contacto de verificación de acoplamiento
English translation:
latch check switch
Added to glossary by
Claudia Luque Bedregal
Apr 23, 2013 05:25
11 yrs ago
2 viewers *
Spanish term
contacto de verificación de acoplamiento
Spanish to English
Tech/Engineering
Electronics / Elect Eng
circuit breakers
Contexto: Especificación técnica para interruptores de potencia
El mecanismo de operación deberá prever el uso de dispositivos de recierre capaces de recerrar el interruptor de acuerdo con lo establecido en las normas. Se deberá incluir un sistema de antibombeo en el circuito del mando y un contacto de verificación del acoplamiento, el cual permita el recierre automático instantáneo.
Gracias por su ayuda.
El mecanismo de operación deberá prever el uso de dispositivos de recierre capaces de recerrar el interruptor de acuerdo con lo establecido en las normas. Se deberá incluir un sistema de antibombeo en el circuito del mando y un contacto de verificación del acoplamiento, el cual permita el recierre automático instantáneo.
Gracias por su ayuda.
Proposed translations
(English)
5 | Latch Check Switch | JoLuGo |
2 | connection verification contact | Neil Ashby |
Proposed translations
15 hrs
Selected
Latch Check Switch
The latch check switch allows the circuit breaker to be used for instantaneous reclosing. The contacts of the latch check switch connect in series with the closing coil. When the guide cam moves out of its normal position, it activates the latch check switch. The closing circuit cannot be energized until the guide cam fully returns to its normal position and the mechanism is in position to allow a close operation.
--------------------------------------------------
Note added at 15 hrs (2013-04-23 20:31:04 GMT)
--------------------------------------------------
reversing the motion of the piston and breaker contacts
--------------------------------------------------
Note added at 15 hrs (2013-04-23 20:49:25 GMT)
--------------------------------------------------
The trip latch switch is supplied with breakers intended for instantaneous reclosing duty. The switch monitors the position of the trip latch and will function to prevent the breaker from closing electrically until the trip latch is reset
--------------------------------------------------
Note added at 15 hrs (2013-04-23 20:31:04 GMT)
--------------------------------------------------
reversing the motion of the piston and breaker contacts
--------------------------------------------------
Note added at 15 hrs (2013-04-23 20:49:25 GMT)
--------------------------------------------------
The trip latch switch is supplied with breakers intended for instantaneous reclosing duty. The switch monitors the position of the trip latch and will function to prevent the breaker from closing electrically until the trip latch is reset
Example sentence:
Special control circuits on breakers are used for high-speed auto-reclosing. After the breaker has been tripped by the protective relays, the trip coil is de-energized and the closing coil is energized well before the end of the opening stroke, thus rever
Note from asker:
Muchas gracias JoLuGo. |
4 KudoZ points awarded for this answer.
Comment: "Gracias por tu ayuda. Saludos."
2 hrs
connection verification contact
...
Note from asker:
Gracias por la sugerencia. |
Discussion
DISPOSITIVOS DE RECIERRE (ANSI Standard Device Number 79)
El relé de reconexión/reenganche/ recierre proporciona reenganche inmediato de un interruptor de accionamiento eléctrico, rearmándose automáticamente si el interruptor permanece cerrado durante un intervalo ajustable predeterminado. Si el interruptor “re-abre “antes del final de este intervalo, la operación de rearme del relé se interrumpe hasta que el interruptor se cierre manualmente.
Este relé de reconexión es aplicable a las estaciones atendidas o no.
en successful reclosing: non-recurrence of the fault following reclosing
es reenganche con éxito
http://www.electropedia.org/iev/iev.nsf/display?openform&iev...
Por tanto, entiendo que se trata de un "contacto auxiliar indicador de reenganche con éxito" (o "efectivo") en el original, y de "auxiliary contact for successful reclosing indication" en inglés.